C215-2H
C215L-A-EU 105 kW / 215 kWh | 0.5 C
Safe and Reliable
- The cabinet is physically separated for safety reasons
- SMS system for multi-layer security
- High-quality and efficient lithium batteries
- Comprehensive lifecycle management
Cost-effective
- Fast power response for virtual power plants, grid connection, and off-grid operation
- Intelligent balancing strategies maintain battery consistency
- Dynamic switching of energy regulation strategies
Flexible Deployment
- Modular design for easy expansion
- Enables centralized deployment, decentralized deployment, and integration with solar storage charging
Intelligent Management
- Collaboration between cloud, edge, and end for 24/7 monitoring, ensuring safe and stable device operation
- Cloud-based big data and intelligent algorithms for flexible system strategy adaptation
| Battery Data | ||
|---|---|---|
|
Cell Type |
|
LFP |
|
Nominal Capacity |
|
280 Ah |
|
Series-Parallel Type |
|
1P240S |
|
Nominal Capacity per Pack |
|
43.008 kWh |
|
Number of Packs |
|
5 |
|
Nominal System Energy Capacity |
|
215.04 kWh |
|
Nominal DC Voltage |
|
768 V |
|
Nominal DC Voltage Range |
|
672~864 V |
|
Nominal DC Current |
|
140 A |
|
AC Data |
|
|
|
Nominal AC Power |
|
105 kW |
|
Nominal AC Voltage |
|
400 Vac |
|
Nominal Frequency |
|
50/60 Hz |
|
Nominal AC Current |
|
152 A |
|
Max. AC Current |
|
167 A |
|
AC Wiring Type |
|
3W/N+PE |
|
Power Factor |
|
-1 ~ 1 |
|
General Data |
|
|
|
DOD |
|
95% |
|
Noise Level |
|
≤75dB |
|
Protection Level |
|
IP 55 (Battery room and PCS room) |
|
Cooling Method |
|
Liquid cooling/heating |
|
Fire Protection System |
|
Aerosol |
|
Operating Temperature Range |
|
-20 ~ 55 °C ( > 45 °C power reduction) |
|
Relative Humidity |
|
5% ~ 95% RH |
|
Maximum Operating Altitude |
|
2000 m |
|
Display |
|
Web/ LED |
|
COM Interfaces |
|
RS485/ Ethernet/ 4G (optional) |
|
Dimensions (L*W*H) |
|
1344*1399*2080 mm |
|
Weight |
|
2450±50 kg |
Internal Product Diagram

[A] - Thermal aerosol fire extinguishers
[B] - Product name labels
[C] - Smoke detectors for fire detection
[D] - Temperature-sensitive fire detectors
[E] - High-voltage control cabinet
[F] - Battery modules
[G] - EMU control unit
[H] - Liquid cooling piping
[I] - Liquid cooler
[J] - Power supply box
[K] - Energy storage conversion system
Communication Architecture

Layout of Various Energy Storage Cabinets

Note: The installation site environment must meet a total air volume ≥ 2260 m³/h.
Project Cases
Grid-side production/renewable energy with storage
Commercial and industrial renewable energy with storage